dc.description.abstract | UR-UVGI (Upper Room Ultraviolet Germicidal Irradiation) systems can be used as an additional countermeasure of ventilation systems against airborne infectious diseases in healthcare-related buildings. In this study, an UR-UVGI system was evaluated using a novel CFD simulation method in a model room used in an experimental case. The results for several cases showed inactivation rate of 98.3 ~ 96.2% for airborne vaccinia virus in the steady state condition. Equivalent air change per hour (EACH) of the UR-UVGI system was 4.5 ~ 16.5 ACH in the decay condition. Heat boxes accelerated the inactivation of airborne virus by UR-UVGI. However, the discrepancy between simulation and experiment results was observed probably because of lack of the detailed experimental conditions. | - |
dc.description.sponsorship | This research was supported by Basic Science Research Program through the National Research Foundation of Korea (NRF) funded by the Ministry of Education (NRF-2017R1D1A1B03033016) | - |
dc.language.iso | eng | - |
dc.publisher | International Society of Indoor Air Quality and Climate | - |
dc.subject.mesh | Air change rates | - |
dc.subject.mesh | Airborne virus | - |
dc.subject.mesh | CFD simulations | - |
dc.subject.mesh | Experimental conditions | - |
dc.subject.mesh | Infectious disease | - |
dc.subject.mesh | Steady-state condition | - |
dc.subject.mesh | Ultraviolet germicidal irradiations | - |
dc.subject.mesh | Ventilation systems | - |
dc.title | Equivalent air change rate by upper room UVGI system | - |
dc.type | Conference | - |
dc.citation.conferenceDate | 2018.7.22. ~ 2018.7.27. | - |
dc.citation.conferenceName | 15th Conference of the International Society of Indoor Air Quality and Climate, INDOOR AIR 2018 | - |
dc.citation.edition | 15th Conference of the International Society of Indoor Air Quality and Climate, INDOOR AIR 2018 | - |
dc.citation.title | 15th Conference of the International Society of Indoor Air Quality and Climate, INDOOR AIR 2018 | - |
dc.identifier.bibliographicCitation | 15th Conference of the International Society of Indoor Air Quality and Climate, INDOOR AIR 2018 | - |
dc.identifier.scopusid | 2-s2.0-85105646273 | - |
dc.subject.keyword | ACH | - |
dc.subject.keyword | Airborne infection | - |
dc.subject.keyword | CFD | - |
dc.subject.keyword | UVGI | - |
dc.type.other | Conference Paper | - |
dc.subject.subarea | Pollution | - |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.