Ajou University repository

Real-time load variability control using energy storage system for demand-side management in South Koreaoa mark
Citations

SCOPUS

7

Citation Export

Publication Year
2021-10-01
Publisher
MDPI
Citation
Energies, Vol.14
Keyword
Demand-side management (DSM)Energy storage system (ESS)Maximum demand controlPeak shavingSynthetic load generation
Mesh Keyword
Customer load profilesDemand-side managementEnergy storage systemMaximum demandMaximum demand controlPeak-shavingReal- timeSouth KoreaStorage systemsSynthetic load generation
All Science Classification Codes (ASJC)
Renewable Energy, Sustainability and the EnvironmentFuel TechnologyEnergy Engineering and Power TechnologyEnergy (miscellaneous)Control and OptimizationElectrical and Electronic Engineering
Abstract
In today’s power systems, the widespread adoption of smart grid applications requires sophisticated control of load variability for effective demand-side management (DSM). Conventional Energy Storage System (ESS)-based DSM methods in South Korea are limited to real-time variability control owing to difficulties with model development using customers’ load profiles from sampling with higher temporal resolution. Herein, this study thus proposes a method of con-trolling the variability of customers’ load profiles for real-time DSM using customer-installed ESSs. To optimize the reserved capacity for the proposed maximum demand control within ESSs, this study also proposes a hybrid method of load generation, which synthesizes approaches based on Markov Transition Matrix (MTM) and Artificial Neuron Network (ANN) to estimate load variations every 15 min and, in turn reserve capacity in ESSs. The proposed ESS-based DSM strategy primarily reserves capacity in ESSs based on estimated variation in load, and performs real-time maximum demand control with the reserved capacity during scheduled peak shaving operations. To validate the proposed methods, this study used load profiles accumulated from industrial and general (i.e., commercial) customers under the time-of-use (TOU) rate. Simulation verified the improved performance of the proposed ESS-based DSM method for all customers, and results of Kolmogorov-Smirnov (K–S) testing indicate advances in the proposed hybrid estimation beyond the stand-alone estimation using the MTM-or ANN-based approach.
ISSN
1996-1073
Language
eng
URI
https://dspace.ajou.ac.kr/dev/handle/2018.oak/32297
DOI
https://doi.org/10.3390/en14196292
Fulltext

Type
Article
Funding
Funding: This research was supported by Dong-A University.
Show full item record

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Jung, Jaesung  Image
Jung, Jaesung 정재성
Department of Electrical and Computer Engineering
Read More

Total Views & Downloads

File Download

  • There are no files associated with this item.