Ajou University repository

Maximizing distributed energy resource hosting capacity of power system in South Korea using integrated feeder, distribution, and transmission systemoa mark
  • Widiputra, Victor ;
  • Kong, Junhyuk ;
  • Yang, Yejin ;
  • Jung, Jaesung ;
  • Broadwater, Robert
Citations

SCOPUS

6

Citation Export

Publication Year
2020-07-01
Publisher
MDPI AG
Citation
Energies, Vol.13
Keyword
Distributed energy resource (DER)Fast voltage stability index (FVSI)Monte Carlo Simulation (MCS)
Mesh Keyword
Distributed energy resourceDistributed Energy ResourcesDistribution systemsFast voltage stability indicesInterconnection standardsOperation and managementTransmission and distribution systemsTransmission systems
All Science Classification Codes (ASJC)
Renewable Energy, Sustainability and the EnvironmentFuel TechnologyEngineering (miscellaneous)Energy Engineering and Power TechnologyEnergy (miscellaneous)Control and OptimizationElectrical and Electronic Engineering
Abstract
Intermittent power generated from renewable distributed energy resource (DER) can create voltage stability problems in the system during peak power production in the low demand period. Thus, the existing standard for operation and management of the distribution system limits the penetration level of the DER and the amount of load in a power system. In this standard, the hosting capacity of the DER is limited to each feeder at a level where the voltage problem does not occur. South Korea applied this standard, thereby making it hard to achieve its DER target. However, by analyzing the voltage stability of an integrated system, the hosting capacity of DER can be increased. Therefore, in this study, the maximum hosting capacity of DER is determined by analyzing an integrated transmission and distribution system. Moreover, the fast voltage stability index (FVSI) is used to verify the determined hosting capacity of DER. For this, the existing interconnection standard of DER at a feeder, distribution system, and transmission system level is investigated. Subsequently, a Monte Carlo simulation is performed to determine the maximum penetration of the DER at a feeder level, while varying the load according to the standard test system in South Korea. The actual load generation profile is used to simulate system conditions in order to determine the maximum DER hosting capacity.
ISSN
1996-1073
Language
eng
URI
https://dspace.ajou.ac.kr/dev/handle/2018.oak/31520
DOI
https://doi.org/10.3390/en13133367
Fulltext

Type
Article
Funding
Funding: This research was supported by Energy AI Convergence Research & Development Program through the National IT Industry Promotion Agency of Korea (NIPA) funded by the Ministry of Science and ICT (No. S1601-20-1005).